Who runs the program
City of Tracy Utilities, Environmental Compliance, 3900 Holly Drive, Tracy, CA 95304, (209) 831-6330, environmentalcompliance@cityoftracy.org. In the code, “‘Director’ means the City of Tracy Director of Utilities or authorized representative” (TMC 5.26.030), and the chapter “shall be known as the FOG control program” (5.26.010(b)). Every section carries the same history line: Ord. No. 1276, adopted 11-19-2019.
Which section applies: 5.26, not 5.24.180
Older City handouts and some search results point restaurants to TMC 5.24.180. The current code does not. Section 5.24.180 is now titled “Oil, sand and lint separators” and governs “service stations, auto repair shops, carwashes, and other facilities”; its subsection (d) says in full: “Food service establishments shall follow chapter 5.26.” If a vendor or a lease quotes 5.24.180 at your kitchen, the rule they mean lives in Chapter 5.26 and reads as below.
Who is covered
The chapter applies “to discharges of wastewater containing FOG conveyed to the public sewer from any commercial or institutional food service establishment” (5.26.020). An FSE is a food facility under Health and Safety Code 113789 that “has any process or device that uses or produces FOG, or grease vapors, steam, fumes, smoke or odors that are required to be removed by mechanical ventilation”; a place limited to “reheating, hot holding or assembly of ready to eat food products” with no significant FOG discharge is not an FSE (5.26.030). If you have a hood, you are in.
When you must install, and what
“Every FSE is required at the time of construction, remodel, and/or change in operations to install, operate and maintain a grease interceptor,” sized “as determined by the most current edition of the California Plumbing Code.” Food-prep and clean-up fixtures and drains connect to it; “Dishwashers shall not be connected to the grease interceptor” (5.26.070). Existing FSEs that caused a grease blockage, sit on a “hot spot” line, or contribute significant FOG “shall install grease interceptors within 180 working days upon notification by the Director” (5.26.070(b)(1)); a change of ownership, remodel or change in operations also triggers installation (b)(2). The unit: California Plumbing Code design, “a minimum of two (2) compartments,” “an access manhole, with a minimum diameter of twenty-four (24) inches ... over each grease interceptor chamber and each sanitary tee,” and grease retention fittings (5.26.080). The Director “may grant a conditional waiver of the requirement to install a grease interceptor” (5.26.100(a)); the chapter’s own cross-reference in 5.26.070 points to 5.26.080 for the waiver, but the waiver section as published is 5.26.100.
The interval, quoted
TMC 5.26.090(a): interceptors “shall be maintained in efficient operating condition by periodic inspection and removal of the full content of the interceptor which includes wastewater, accumulated FOG, floating materials, sludge and solids.” The frequency is “approved by the Director” (b) and determined under (e):
- “(1) Grease interceptors shall be fully pumped out and cleaned at a frequency such that the combined FOG and solids accumulation does not exceed twenty-five (25) percent of the total design hydraulic depth of the grease interceptor.”
- “(2) All FSEs with a grease interceptor shall maintain their grease interceptor not less than every six (6) months.”
- “(3) Grease interceptors shall be fully pumped out and cleaned quarterly when the frequency described in subsection (e)(1) has not been established,” adjusted “when sufficient data have been obtained to establish an average frequency.” “The city may change the maintenance frequency at any time.”
- (4) You “may submit a request to the Director requesting a change in the maintenance frequency at any time.”
- (5) Over 25% at any time means the interceptor must be “serviced immediately such that all fats, oils, grease, sludge, and other materials are completely removed.”
Read together: a new or unmeasured tank is on a quarterly schedule; once depth readings show how fast you reach 25%, the Director can approve a frequency built on them; nothing stretches past six months; and operating over 25% is itself a prohibited act, “The grease and solids layers combined shall not exceed twenty-five (25) percent of the total interceptor liquid depth” (5.26.040(g)). Removed material “shall be disposed of off-site properly by wastehaulers” (5.26.090(f)). The City’s pamphlet adds the practical version: “Depending on site conditions interceptors should be cleaned every few weeks to every 3 months,” traps “every day to every few weeks,” and “When the volume of the device is 25% full of FOG and food solids it needs to be cleaned.” The calculator estimates your days-to-25%.
Other prohibitions
- Food grinders: banned in new FSE construction and to be removed from existing FSEs “within 180 working days of the effective date of this chapter” unless the Director allows in writing (5.26.040(a)).
- Additives “for the purpose of emulsifying FOG or biologically/chemically treating FOG” without written authorization (b).
- Waste cooking oil to the sewer or storm drain (c); wastewater over 140°F into any interceptor or grease control device (d); diluting a discharge to pass (h).
- Discharging FOG that exceeds the council’s adopted limit or “may accumulate and/or cause or contribute to blockages” (5.26.050).
Records: the City’s binder
TMC 5.26.160: “The FSE and property owner shall be required to maintain on the FSE premises copies of all manifests, receipts and invoices of all cleaning, maintenance, grease removal of/from the grease control device, disposal carrier and disposal site location for no less than three (3) years,” available on request “to the Director, any inspector and/or enforcement officer, and the public.” The records “shall be kept in the binder provided by the city” and include cleaning and maintenance records, BMP and employee-training records, wastehauling manifests, “sludge height monitoring for FOG and solids accumulation,” spill and lateral-cleaning records, and anything else the Director requires. The City’s Grease Removal Device Cleaning and Maintenance Log is printed “In accordance with, T.M.C. 5.26.160.” Our receipt gives you the depth reading that log wants and the manifest the binder wants.
Fees the City publishes
| Citywide Master Fee Schedule, Environmental Compliance | FY 2025-26 | FY 2026-27 (from July 1, 2026) |
|---|---|---|
| FSE / FOG annual inspection and annual permit, small generator | $176 | $181 |
| Same, medium generator | $226 | $233 |
| Same, large generator | $318 | $328 |
| Re-inspection / sampling / non-compliance inspection, per inspection | $212 | $218 |
The City’s FOG booklet still prints a $207 re-inspection minimum; that figure predates both schedules above. The small/medium/large generator definitions are not quoted on this site; Environmental Compliance assigns your tier. Under 5.26.190 a noncompliance charge is “in the amount reasonably determined by the Director” (e), and FSEs holding a waiver pay “an annual grease disposal mitigation fee” (f).
Enforcement
“Any violation of this chapter is considered a public nuisance” (5.26.260). Civil penalties: “a minimum penalty of one thousand and no/100ths ($1,000.00) dollars per day for each day such violation occurs” (b). Violations “may be charged as infractions or misdemeanors, at the discretion of the City Attorney” (c), and the Director “is authorized to issue notices of violation, administrative citations and impose administrative civil penalties pursuant to chapter 1.04” (d). The chapter also carries suspension and termination sections (5.26.230 through 5.26.250). The booklet’s summary: “Failure to comply could lead to monetary penalties (minimum $1,000 per day/per violation) or ordered to cease discharge.”
What we do not quote here
The City’s newer Food Service Establishments web page and the definitions of small, medium and large generator are not quoted on this site. Environmental Compliance at (209) 831-6330 can tell you your tier and your current approved frequency. The booklet also notes a “Preferred Pumper Program ... Currently, not available in our region,” so there is no City-approved hauler list to check us against; check the receipt instead.
How we service Tracy kitchens
Every visit starts with a depth reading, because that reading is the (e)(1) data that lets your frequency move off the quarterly default. Then the full content out as 5.26.090(a) defines it: wastewater, FOG, floating material, sludge and solids; baffles and tees checked; refilled. The receipt carries the percent-full reading, gallons removed, repairs needed and the disposal site, and goes in the City’s binder. Same truck as Stockton, where the rule is three months or 25%; in Tracy the same reading answers a six-month ceiling and a quarterly default.
Tracy: quarterly, or your own number
Tank size and meals per day. The first reading starts the data that sets your frequency.
Call (209) 292-2953